Ziton Galvanic Isolator Unit for 670 series conventional systems

SKU
GBX2000
£373.79 £311.49
Ziton I.S. Isolated Barrier For Conventional Systems (GBX2000 )

The Ziton GBX2000 is a galvanic isolation barrier selected specifically for use between an Intrinsically safe conventional zone and a zone-monitor.

Every GBX2000 (4 terminals) functions like a "DC current isolator" with reverse polarity protection. The input and output are galvanically isolated from each other. It is designed for the connection of fire detectors, smoke detectors, temperature sensors, etc. A detector's increased current range and the higher accuracy allow for differentiation between normal operation, fire alarm, lead breakage and short circuit currents in the safe area. In many cases they may also be used for controlling I/P converters. A separate power supply with auxiliary power is not required. Due to the input voltage limiting of 24 V, the maximum voltage output is 21 V.


Key Features
> Approved with the IU2055 zone monitor unit
> Output EEx ia IIC
> Device installation permissible in zone 2
> Polarity reversal protected
> Accuracy 1%
> EMC acc. to NAMUR NE 21
> Up to SIL2 acc. to IEC 61508
More Information
ManufacturerZiton
MPNGBX2000
Write Your Own Review
You're reviewing:Ziton Galvanic Isolator Unit for 670 series conventional systems
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Code: GBX2000
Description: Ziton I.S. Isolated Barrier for Conventional Systems
Dimensions: W:20mm x H:107mm x D:115mm
Operating voltage: 4 to 35 VDC
Inputs/Outputs (not intrinsically safe):
Current: 0 to 40 mA
Power loss: at 40 mA and Uin < 22 V: 700 mW at 40 mA and Uin > 22V: 1.2 W
Inputs/Outputs (intrinsically safe): Voltage: for 4 V < Uin < 24 V: >= Uin - (0.37 x current in mA) - 1.0 for Uin > 24 V: = 21 V - (0.36 x current in mA)
Short-circuit current: at Uin > 24 V: >= 65 mA
Transfer current: <= 40 mA
Ambient temperature:
-20°C to +60°C
Group, category, type of protection: II (1) G D [EEx ia] IIC (-20°C <= Tamb <= 60°C)
Type of protection [EEx ia]: Explosion group: IIA IIB IIC
External capacitance: 2.9 µF 0.82 µF 0.107 µF
External inductance: 33 mH 18 mH 4.3 mH
Mounting type: DIN rail
Regulatory: CENELEC/ATEX certified
Weight: 100g
Ziton Galvanic Isolator Unit for 670 series conventional systems