Ziton Conventional IS heat detector weatherproof 57oC
The Ziton Enclosed Conventional Heat Detector, Weatherproof IP67, 57°C, Class A2S (54 to 70°C) is normally used in rooms where the temperature can be expected to rise rapidly in case of a fire or in places where smoke detectors cannot be used. It is intended for outdoor or indoor use in high humidity areas.
A conventional fixed temperature heat detector, i.e. it will give an alarm within a response temperature range in accordance with EN54-5:2000. The sensing element is a heat pick-up shield and a bi-metal switch. An LED on the detector will light up when the detector activates. Supports an output for a remote indicator.
The detector is latching, i.e. it will not be automatically reset if the temperature, after the alarm, falls below the detector's static response temperature. An LED and a connected remote LED will be lit until the detector is reset via the C.I.E.
All electronic components are mounted in a grey waterproof detector housing and fitted to the supplied connection box. The connection box has three cable inlets. Three compression glands and a silicon gasket for IP67 protection are supplied with the product. 3 pairs of flying leads with female push-on connectors to connect the zone line cables (in / out) and the remote indicator are provided.
Key Features |
---|
> Fixed temperature alarm level > Waterproof (IP67) > Enclosed > 57°C, Class A2S |
Manufacturer | Ziton |
---|---|
MPN | 6295 |
Write Your Own Review
![Loading...](https://www.safefiredirect.co.uk/static/version1719466362/frontend/Alothemes/electro2s/en_GB/MageArray_ProductQuestions/images/loader.gif)
Sort By:
No questions yet. Be the first to ask the question!
Code: | 6295 |
Description: | Ziton Enclosed Conventional Heat Detector, Weatherproof IP67, 57°C, Class A2S |
Dimensions: | Dia:100mm x D:75mm |
Operating voltage: | 12 to 30 VDC (24 VDC) |
Current consumption: | 0 mA (Quiescent) 6 to 40 mA (±400 Ω) (Alarm, Internal Resistance) |
Static response temperature: | 57°C |
Operating temperature: | -40 to +50ºC |
Storage temperature: | -45 to +70°C |
IP rating: | IP67 Exd, Indoor, Outdoor |
Colour: | Grey |
Construction: | Modified polycarbonate |
Remote indicator: | Supply-2VDC 10 mA |
Regulatory: | CE, CENELEC/ATEX, CPD, EN54-5 II 3 G Ex ic IIC T5 Gc, II 3 D Ex ic IIIC T100°C Dc -40°C ≤ Ta ≤ 50°C / EN 60079-0:2009, EN 60079-11:2012 |
Weight: | 216 g |