This website uses cookies to ensure you get the best experience on our website. Read our cookie policy
SKU
ZP2-F2-FB2
£740.42 £617.02
Ziton Addressable Fire Panel with Fire Brigade Controls - 2 Loop (ZP2-F2-FB2)
The Ziton ZP2-F2-FB2 is an Addressable, 2 loop Fire Panel with user interface and fire routing controls that supports up to 256 devices in 128 zones. It has 4 supervised sounder/fire-routing outputs, which can also be used as freely programmable outputs. In addition, there are 2 conventional relay outputs and 2 supervised outputs, working in pairs and dedicated to common fire and fault condition. 2 user configurable inputs for monitoring and control are also available.
Key Features |
---|
> 2 loops expandable to 4 with up to 512 zones with Fire Brigade & Fire Protection controls and 300 output groups > Up to 40 LED Zone indicators for Fire and Fault with ample text space > Auto configuration, setup wizard and default regional setup modes > Ethernet port with TCP/IP for remote diagnostics, maintenance and programming > EN54 compliant graphical LCD with icons and up to 256 zones > Jog Dial with 4 soft buttons for simple and intuitive user control > Pleasing design with special paintable synthetic door > Easy removable door and chassis for quick and clean installation > All pluggable connectors > 3 USB ports with memory stick support and RS232 for printer support > Email notification for events directly from the panel (4 user accounts) > Auxiliary 24VDC supply output with reset support > 3 operator level menu structure (20 usernames and passwords) > History log memory for 9999 events > Up to 72 hours standby time and 30 minutes alarm > Compatible with the new loop powered sounders/beacons and base sounders and the 2000 series detectors with replaceable optical chamber |
Manufacturer | Ziton |
---|---|
MPN | ZP2-F2-FB2 |
Write Your Own Review
![Loading...](https://www.safefiredirect.co.uk/static/version1719466362/frontend/Alothemes/electro2s/en_GB/MageArray_ProductQuestions/images/loader.gif)
Sort By:
No questions yet. Be the first to ask the question!
Code: | ZP2-F2-FB2 |
Description: | Ziton Addressable Fire Panel with Fire Brigade Controls - 2 Loop |
Dimensions: | W:450mm x H:550mm x D:172mm |
Form factor: | Large |
Operating voltage: | 110 /230 VAC (+10%/-15%) |
Current consumption: | Nom. 0.6 / 1.3 A, Max. 1.5 / 3.15 A |
Network size (nodes): | up to 64 |
Max. system capacity: | up to 32512 devices |
Max. loop capacity: | 4 |
Max. zone capacity: | up to 512 |
Mains frequency: | 50 / 60 Hz (±5%) |
Fuse rating: | 2 / 4 A |
Cable type: | 3 x 1.5 mm² (live, neutral, earth) |
INPUT | |
Cable type: | Recommended 2 core 1.5 mm² twisted pair |
Programmable: | 2 |
End of line resistor: | 15 kohm |
Max. load: | 150 mA |
OUTPUT | |
Programmable supervised: | 4, 750mA / 19.5-28VDC (24VDC nominal) |
General Fire + Fault supervised: | 2, 350mA / 19.5-28VDC (24 VDC nominal) |
General Fire + Fault relay: | 2 |
Auxiliary power: | 1 resettable, 500 mA / 19.5 to 28 VDC (24 VDC nominal) |
Cable type: | Recommended 2 core 1.5 mm² twisted pair |
End of line resistor: | 15 kohm |
Loop output: | 2, 250 mA / 29VDC (29VDC to 36VDC ) |
Loop cable length: | 75ohm / 500nF max. 2 km |
Loop cable type: | Recommended 2 core 1.5 mm² twisted pair |
STANDBY BATTERY | |
Capacity: | Max. 2 x 12 V / 18 Ah (use supplied cables) |
Mounting type: | Surface |
Operating temperature: | -8 to +42°C |
Storage temperature: | -10 to +50°C |
Relative humidity: | 95% max. non condensing |
IP rating: | IP30, indoor use only |
Colour: | Grey (RAL 7035) |
Cable entries: | 18 (20mm) / 2 (20mm) / 2 removable plates (Top/Bottom/Back) |
Regulatory: | BS5839-1, CPD, LPCB, NBNS21-100, NEN2535, RoHS, WEEE compliant EN54-13, EN54-2, EN54-21, EN54-4, VdS certified |
Weight: | 10.1kg (7.4kg without battery) |