Siemens FC724-ZA-P Cerberus PRO 4 Loop Fire Panel in Comfort Housing c/w 1.5A Power Loop Module (No Zonal LEDs)
SKU
S54433-C115-A1
£2,190.01 £1,825.01
Siemens 4-Loop Fire Control Panel, Comfort Housing (2 x 12v 26Ah Batteries) No zonal LEDs & c/w C-NET, P 1.5A Module (S54433-C115-A1)
The Siemens Cerberus PRO FC724-ZA (4-loop with 1.5 A linedriver, expandable to 8) is a compact fire control panel with an integrated operating unit that can process signals from Cerberus PRO devices of up to 504 addresses.
The fire control panel can be used as a stand-alone version or networked. It can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire terminals can be connected in a single cluster (C-WEB/SAFEDLINK network), or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked.
This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals.
All detector lines are monitored for ground faults.
Adaptation of the user text directly on the terminal or with the Cerberus-Engineering-Tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change.
Detection and automatic read-in (auto configuration) of all C-NET devices, providing immediate simple operation.
Stored data can be uploaded via Cerberus-Remote access.
The FC724-ZA is ideally suited for large-sized applications, e.g. in industrial plants, regional banks, office complexes, etc. The FC724-ZA with flexible cross linking possibilities can also be used for extensive systems.
The expansion and accessories must be ordered separately.
Key Features |
---|
> 4-loop Fire Control Panel with 1.5A line driver, expandable to 8 > Comfort housing > No zonal LEDs > Space for 2 x 26Ah batteries > Processes signals from up to 504 addresses > May be used as a stand-alone unit or networked > Ethernet connection available at each station > Programmable via Cerberus-Engineering-Tool > Detector lines monitored for ground faults > Auto configuration of all C-NET devices > Stored data can be uploaded via Cerberus-Remote access > Suited to large sized applications e.g. industrial plants, office complexes or when networked as part of larger applications > Expansions and accessories must be ordered separately |
Manufacturer | Siemens |
---|---|
MPN | FC724-ZA-P |
Primary Power Source | Mains Powered (230V) |
System Type | Addressable |
Number of Loops | 4 |
Protocol Compatibility | Siemens Cerberus |
Colour | Grey |
Warranty | 5 Years |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Product: | Siemens 4-Loop Fire Control Panel, Comfort housing, no zonal LEDs, P 1.5A line driver |
Product code: | S54433-C115-A1 |
Dimensions: Without cover cap: With cover cap: | W:430mm x H:796mm x D:160mm W:430mm x H:796mm x D:183mm |
Detector compatibility: | Cerberus™ PRO FD720 |
Operating voltage: | 21 - 28.4V |
No. of addresses: | 504 |
No. of detector lines: | 4 (8) loops or 8 (16) stub lines |
Battery capacity: | Max. 2 x 12V, 25 Ah |
Programmable input/output: | 12 |
Relay outputs: | 1 x RT alarm 1 x RT fault |
Supervised output: | 1 x RT alarm 1 x RT fault 2 x Horn |
Power supply: | 150W |
Operating current: | 5000 mA |
Mains voltage: | AC 115 / 230 V +10/-15 % |
Bypass time for emergency power supply: | 72h |
Plug-in position: | 2 -> for serial interfaces RS232, RS485 , 2 -> for network modules , 2 -> for loop extension (C-NET) |
Relative humidity: | ≤95 % rel. (no condensation) |
Operating temperature: | -8 to 42 °C |
Storage temperature: | -20 to +60 °C |
Protection category: | IP30 |
Colour housing/cover: | Light Grey RAL 7035 / Grey RAL 050 00 00 |