Siemens FC722-ZZ-P Cerberus PRO 2 Loop Fire Panel in Standard Housing c/w 1.5A Power Loop Module (No Zonal LEDs)

SKU
S54433-C113-A1
£1,367.68 £1,139.73
Siemens 2 Loop Fire Control panel in Standard Housing (2 x 12v 12Ah Batteries) No zonal LEDs, c/w C-NET, P 1.5A Module (S54433-C113-A1)

The Siemens Cerberus PRO FC722-ZZ-P (2-loop with 1.5 A line driver, expandable to 4) is a compact fire control panel with an integrated operating unit that can process signals from Cerberus PRO devices of up to 252 addresses.

The fire control panel can be used as a stand-alone version or networked. It can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire terminals can be connected in a single cluster (C-WEB/SAFEDLINK network), or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. 

This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals.

* All detector lines are monitored for ground faults.
* Adaptation of the user text directly on the terminal or with the Cerberus-Engineering-Tool.
* Up to 2000 events can be stored according to various criteria.
* Automatic summer/winter time change.
* Detection and automatic read-in (auto configuration) of all C-NET devices, providing immediate simple operation.
* Stored data can be uploaded via Cerberus-Remote access.

The FC722-ZZ is ideally suited for medium-sized applications, e.g. in workshops, hotels, etc. or when networked as part of much larger applications. The FC722-ZZ with flexible cross-linking possibilities can also be used for extensive systems.

The expansion and accessories must be ordered separately.


Key Features
> 2-loop Fire Control Panel, expandable to 4
> P 1.5A line driver
> Standard housing
> No zonal LEDs
> Space for 2 x 12Ah batteries
> Processes signals from up to 252 addresses
> May be used as a stand-alone unit or networked
> Ethernet connection available at each station
> Programmable via Cerberus-Engineering-Tool
> Detector lines monitored for ground faults
> Auto configuration of all C-NET devices
> Stored data can be uploaded via Cerberus-Remote access
> Suited to medium sized applications e.g. workshops, hotels or when networked as part of larger applications
> Expansions and accessories must be ordered separately
More Information
ManufacturerSiemens
MPNFC722-ZZ-P
Primary Power SourceMains Powered (230V)
System TypeAddressable
Number of Loops2
Number of Zones24
Protocol CompatibilitySiemens Cerberus
ColourGrey
Warranty5 Years
Write Your Own Review
You're reviewing:Siemens FC722-ZZ-P Cerberus PRO 2 Loop Fire Panel in Standard Housing c/w 1.5A Power Loop Module (No Zonal LEDs)
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Product: Siemens 2-loop Fire Control Panel, 2 x 12Ah batteries, No zonal LEDs, Standard housing, c/w C-NET P1.5A
Product code: S54433-C113-A1
Dimensions:
Without cover cap:
With cover cap:

W:430mm x H:398mm x D:160mm
W:430mm x H:398mm x D:183mm
Detector compatibility: Cerberus™ PRO FD720
Operating voltage: 20.5 - 28.6V
No. of addresses: 504
No. of detector lines: Loops: 2 (4) Stub lines: 4 (8)
Battery capacity: Max. 2 x 12V, 12 Ah
Programmable input/output: 8
Relay outputs: 1 x RT alarm 1 x RT fault
Supervised output: 1 x RT alarm 1 x RT fault 1 x Horn
Power supply: 70W
Operating current: 2500 mA
Mains voltage:
 AC 97-127 V / AC 196-253 V
Bypass time for emergency power supply: 72h
Plug-in position: 2 -> for serial interfaces RS232, RS485 , 2 -> for network modules , 1 -> for loop extension (C-NET)
Relative humidity: ≤95 % rel. (no condensation)
Operating temperature: -8 to 42 °C
Storage temperature: -20 to +60 °C
Protection category: IP30
Colour housing/cover: Light Grey RAL 7035 / Grey RAL 050 00 00
Weight: 10.6 kg
Siemens FC722-ZZ-P Cerberus PRO 2 Loop Fire Panel in Standard Housing c/w 1.5A Power Loop Module (No Zonal LEDs)