This website uses cookies to ensure you get the best experience on our website. Read our cookie policy
Siemens FC722-YZ-P Cerberus PRO 2 Loop Fire Panel in Standard Housing c/w 1.5A Power Loop Module (c/w 24 Zone LEDs)
SKU
S54433-C113-A2
£1,786.94 £1,489.12
Siemens 2 Loop Fire Control panel in Standard Housing (2 x 12v 12Ah Batteries), c/w C-NET, P 1.5A Module & 24z LEDs (S54433-C113-A2)
The Siemens Cerberus PRO FC722-YZ-P (2-loop with 1.5 A line driver, expandable to 4) is a compact fire control panel with an integrated operating unit that can process signals from Cerberus PRO devices of up to 252 addresses.
The fire control panel can be used as a stand-alone version or networked. It can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire terminals can be connected in a single cluster (C-WEB/SAFEDLINK network), or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked.
This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals.
* All detector lines are monitored for ground faults.
* Adaptation of the user text directly on the terminal or with the Cerberus-Engineering-Tool.
* Up to 2000 events can be stored according to various criteria.
* Automatic summer/winter time change.
* Detection and automatic read-in (auto configuration) of all C-NET devices, providing immediate simple operation.
* Stored data can be uploaded via Cerberus-Remote access.
The FC722-YZ-P is ideally suited for medium-sized applications, e.g. in workshops, hotels, etc. or when networked as part of much larger applications. The FC722-ZZ with flexible cross-linking possibilities can also be used for extensive systems.
The expansion and accessories must be ordered separately.
Key Features |
---|
> 2-loop Fire Control Panel, expandable to 4 > P 1.5A line driver > Standard housing > c/w 24 zonal LEDs > Space for 2 x 12Ah batteries > Processes signals from up to 252 addresses > May be used as a stand-alone unit or networked > Ethernet connection available at each station > Programmable via Cerberus-Engineering-Tool > Detector lines monitored for ground faults > Auto configuration of all C-NET devices > Stored data can be uploaded via Cerberus-Remote access > Suited to medium sized applications e.g. workshops, hotels or when networked as part of larger applications > Expansions and accessories must be ordered separately |
Manufacturer | Siemens |
---|---|
MPN | FC722-ZZ-P |
Primary Power Source | Mains Powered (230V) |
System Type | Addressable |
Number of Loops | 2 |
Number of Zones | 24 |
Protocol Compatibility | Siemens Cerberus |
Colour | Grey |
Warranty | 5 Years |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Product: | Siemens 2-loop Fire Control Panel, 2 x 12Ah batteries, No zonal LEDs, Standard housing, c/w C-NET P1.5A |
Product code: | S54433-C113-A1 |
Dimensions: Without cover cap: With cover cap: | W:430mm x H:398mm x D:160mm W:430mm x H:398mm x D:183mm |
Detector compatibility: | Cerberus™ PRO FD720 |
Operating voltage: | 20.5 - 28.6V |
No. of addresses: | 504 |
No. of detector lines: | Loops: 2 (4) Stub lines: 4 (8) |
Battery capacity: | Max. 2 x 12V, 12 Ah |
Programmable input/output: | 8 |
Relay outputs: | 1 x RT alarm 1 x RT fault |
Supervised output: | 1 x RT alarm 1 x RT fault 1 x Horn |
Power supply: | 70W |
Operating current: | 2500 mA |
Mains voltage: | AC 97-127 V / AC 196-253 V |
Bypass time for emergency power supply: | 72h |
Plug-in position: | 2 -> for serial interfaces RS232, RS485 , 2 -> for network modules , 1 -> for loop extension (C-NET) |
Relative humidity: | ≤95 % rel. (no condensation) |
Operating temperature: | -8 to 42 °C |
Storage temperature: | -20 to +60 °C |
Protection category: | IP30 |
Colour housing/cover: | Light Grey RAL 7035 / Grey RAL 050 00 00 |
Weight: | 10.6 kg |