The Nittan evo+5802 is a 2-8 loop addressable fire alarm panel fitted with 2 loop cards for Nittan Evolution protocol and a standard network card.
The evo+5800 series is fully expandable from 2 to 8 loops and supplied with 8 on-board sounder circuits, 20 programmable zonal LEDs with slide-in labels, and 25 System LEDs for information purposes. There are also 4 programmable function buttons with LED indication for confirmation of operation.
The control panel consists of the latest dual flash-based microprocessor technology combined with a high resolution, high contrast, graphical LCD display and tactile keypad providing a simple ‘select and click’ programming aid for engineer configuration and end-user operation.
Powerful cause-and-effect programming coupled with dynamic zoning and enhanced trace diagnostics makes the panel suitable for a wide range of site applications from small to large complex multi-area systems. Fully programmable onsite via the on-board alphanumeric keypad, or PC-NeT configuration software.
PC Software
An extensive suite of user-friendly Windows based PC software programs has been developed to enhance your experience when using evo+5800 series fire panels. The suite incorporates a number of different programmes to include a configuration, service, logo and virtual panel tool to allow the flexibility of the equipment to be fully explored.
Network
Simply adding a network card allows the panel to communicate with any other evo+ fire panel, remote terminal, or network peripheral, such as, ipGateway™ or BMS/graphical interface. The network operates as a true peer-to-peer system and can be configured in a fault-tolerant loop or radial format.
Key Features |
---|
> c/w 2 Loop Cards fitted (expandable up to 8 loops with additional loop cards) > c/w Standard Network Card > 20 programmable Zonal / 25 System LEDs > Nittan Evolution protocol > Graphical LCD user interface and support for up to 200 fire zones by default allowing full EN54 compliance without additional hardware > Dedicated USB & RS232 serial port for direct PC or modem connection > Installer friendly Auto-learn, Loop Detection and Onboard Scope facility for ease of commissioning and fault finding > The graphical display can be configured to operate with virtually any language or character set > Integral P-Bus for system expansion via available option cards > Ad-NeT peer-to-peer network with up to 2000 zones > Approved to BS EN54 part 2 and 4 > Robust removable equipment chassis with plug-in connectors for simple fixing and cable termination |
Manufacturer | Nittan |
---|---|
MPN | F12N95802 |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Base Technology | Dual flash-based processors with real-time clock, trace diagnostics, programmable languages and character sets |
Display | White backlit 240 x 64 graphical LCD |
LED Indicators | 22 red (1 x Fire, 1 x More Alarms, 20 x Zonal Programmable), 1 green (Power), 13 amber and 12 bi-colour (Fault & System) |
Controls | Alpha numeric keypad permitting navigation, Reset, Mute, Silence, Resound, Evacuate, and 4 x Programmable push buttons |
Protocols | Nittan Evolution |
Number of Fire Zones | 2000 (200 per individual panel) |
Number of Loops | Dedicated 2-8 loop control panel |
Devices per Loop | Max 254 |
Loop Current | 500mA per loop |
On-Board Sounder Circuits | 8 x 1 Amp programmable |
On-Board Relays | 4 x 1 Amp 30v AC/DC programmable(10mA, 5v min) - expandable to 8 using 2 x Mxp-507 |
Auxiliary Supply | 2 x 24v 500mA 2 |
Programmable Input | 2 x monitored programmable input on-board |
Programmable Key Switch Inputs | 16 volt free inputs |
Total Available Output Current | 2 x 5A maximum available for loop current + sounder outputs + auxiliary supply |
Mains Supply | 200 - 240v 47-63 Hz AC (+10%, -15% tolerance) 1.4A Max |
Battery Capacity | 2 x 24V 4Ah internal (min), 2 x 24V 18Ah internal (max), or 1 x 24v 45Ah internal (max) and 1 x 24v, 45Ah external (max) |
Charger Current | 2 x 2A temperature compensated |
Serial Port | 2 x on-board RS232 connection for PC, modem, IP, or portable printer |
USB Interface | 2 x USB B type connection for PC communication |
Programming | On-board keypad or PC running Windows tools |
Event Log | 2 x 5000 event & diagnostic + 500 fire |
Networking | Optional plug-in network card (Mxp-503 - standard, or Mxp-509 - fault-tolerant) |
Printer (optional) | On-board |
Enclosure / Colour | Steel IP30 / RAL7035 |
Cable Entry (20mm knockouts) | 30 x top, 6 x rear, 3 x bottom, plus 2 x double knockout rear |
Size H x W x D mm | 750 x 450 x 190 |
Metalwork Options | Semi-flushing bezel, battery box, utility enclosure, termination enclosure and rack mount |
Approvals | EN 54-2:1998, EN 54-4:1998, EN 54-13:2005 |