Kentec Syncro AS 1-2 Loop Fire Panel c/w 1 Loop Card + Enable Keyswitch (Apollo Protocol) (A80161M2)
The Kentec A80161M2 Syncro AS is a 1-2 loop addressable fire panel with 1 loop card fitted (expandable to 2 loops with additional loop card) and an enable controls keyswitch fitted. The panel is compatible with Apollo XP95 / Discovery protocol devices.
Syncro AS is an analogue addressable fire control panel, available in either one or two detection loops. It combines compact and practical styling with the programming power and connectivity normally associated with much larger systems.
With its ease of use and simplicity to install, Syncro AS is straightforward to understand for installers, commissioning engineers and end users alike. Using the latest microprocessor, it provides a flexible control system with high reliability and integrity.
The Syncro AS panels are ideal for small and medium sites that require advanced fire sensing and evacuation options. It can be expanded and networked to become part of much larger systems if the need arises (except AS Lite panels), therefore providing a future proof solution for any size of installation.
Key Features |
---|
> 1-2 loop addressable fire panel c/w 1 loop card - Apollo XP95 / Discovery protocol > Expandable from 1 to 2 loops with additional loop card (sold separately) > Fitted with enable controls keyswitch > Network up to 64 panels > Compatible with Syncro View repeaters > Up to 512 additional programmable I/O via Syncro I/O modules > 3A power supply > 2 programmable sounder circuits > 5 programmable inputs > 3 programmable relays > Sensitivity adjustment and Drift Compensation > Stores 500 last events in event log > Powerful, network wide cause and effects > Installer friendly, removable equipment chassis > Different language and character set variants available > Approved and certified to EN54-2/ EN54-4 |
Manufacturer | Kentec Electronics |
---|---|
MPN | A80161M2 |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Construction | 1.2mm mild sheet steel |
IP Rating | IP30 |
Finish | Epoxy powder coated |
Colour - lid & box | BS 00 A 05 grey - fine texture |
Colours - control plates & labels | RAL 7047 light grey - satin |
Weight | 6kg (standard panel) |
Dimensions (WxHxD) | 385mm x 310mm x 90mm |
Display | 8 lines of 40 characters graphic LCD |
Mains voltage supply | 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V) |
Mains supply fuse | 1.6A 250V |
Power supply DC rating | 24V 3 Amps |
Aux 25V supply | Fused at 500 milliamps |
Maximum battery size | 9Ah 12V (2 per panel) (non-networked) |
Fault contact rating | 30V DC 1 Amp |
Fire contact rating | 30V DC 1 Amp |
Alarm contact rating | 30V DC 1 Amp |
Sounder output rating | Fused at 1 Amp each |
Detection loop | 400 milliamp output |
Detector protocols | Apollo XP95 / Discovery |
Printer port | Serial RS232 |
Serial expansion port | Serial RS485 (Compatible with all Syncro I/O modules) |
PC port | Serial RS232 |
Network connection | RS485 - Up to 64 panels via fully fault tolerant optional network card |
Remote Silence input (SIL) | Switched -ve |
Remote fault input (FLT) | Switched -ve |
Remote reset input (RES) | Switched -ve |
Remote alert input (INT) | Switched -ve |
Remote evacuate input (CNT) | Switched -ve |
Download lead | Standard S187, X187LS economy |
Configuration | Via Loop Explorer PC utility |
PC graphics | Via Ockular |
Modem | Optional dial up modem for remote diagnostics (Can be fitted to M3 size enclosure only) |