This website uses cookies to ensure you get the best experience on our website. Read our cookie policy
SKU
HCP-EM(SCI)
£41.42 £34.52
Hochiki HCP-EM(SCI) Marine Approved Addressable Manual Call Point with SCI (Red)
- Buy 10 for £40.78 £33.98 each and save 2%
- Buy 20 for £40.14 £33.45 each and save 3%
- Buy 50 for £39.50 £32.92 each and save 5%
The Hochiki HCP-EM(SCI) is a Marine Approved Manual Call Point with integral short-circuit isolator, which is fully compatible with Hochiki ESP analogue addressable protocol.
The unit incorporates a bi-coloured LED, which can be selected as pulsing/non-pulsing for communications polling (1) and is continuously lit when the HCP-EM(SCI) is operated. In these two states the LED will show red.
The LED will show amber when a short-circuit is present but will switch to red if the unit is activated.
The unit operates by pressing the EN54 compliant non-frangible (plastic) element and produces a high level ESP interrupt.
A built in test function initiated by the control panel ensures the integrity of the device at all times and the device can be tested by insertion of a test key in the underside of the unit.
Two terminal blocks are provided for easy connection to the loop wiring.
The unit is addressed using the TCH-B200 Hand Held Programmer for quick and reliable addressing.
Key Features |
---|
> Marine Approved Addressable Manual Call Point with SCI (Red) > Fast response > Integral short-circuit isolator > Bi-coloured status LED > Non-frangible element fitted as standard (conforms to EN54) > Addressed with TCH-B200 Hand Held Programmer > LPCB Approved to EN54 |
Manufacturer | Hochiki |
---|---|
MPN | HCP-EM(SCI) |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Operating Voltage | 17 – 41 VDC |
Low Power Mode (typ) | 180 µA (max), 100 µA (typ) |
Quiescent Current | 350 µA (max), 250 µA (typ) |
Alarm Current | 10.0 mA (max), 5 mA (typ) |
Resistance in Positive | 100 mΩ when closed (max), 100 kΩ when open (min) |
Short-circuit Threshold (typ) | 430 Ω |
Transmission Method | Digital Communication Using ESP |
Operating Temperature Range | -10 °C to + 50 °C |
Storage Temperature Range | -30 °C to + 70 °C |
Maximum Humidity | 95% RH - Non Condensing (at 40 °C) |
Ingress Protection Rating | IP24 |
Colour / Case Material | Red / Modified Polyphenylene Oxide |
Weight (g) / Dimensions (mm) | (Flush Unit) 110 / W 89 x H 93 x D 27.5 |
(With Surface Mount Back Box) 161 / W 89 x H 93 x D 59.5 |