Fireray 3000 Exd End-to-End Explosion Proof Beam Smoke Detector Kit (3000-115)
The Fireray® 3000 Exd is an End-to-End Explosive Proof Beam Smoke Detector system (3000-115). It comprises a separate, safe area, wall-mounted remote/low level control unit to allow adjustment and testing from a convenient non-hazardous location, an explosion proof infrared transmitter and receiver both of which are ATEX-certified for use in Group 2 hazardous areas as well as 2x surface mount wall brackets.
The product is designed for large enclosures within oil rigs, refineries, ordnance stores and similar premises. It provides an early warning of smouldering or strongly smoke-generative fires, which may not be picked up by flame detectors installed in many hazardous areas.
Key Features |
---|
> Separate transmitter and receiver unit certified to Exd > Allows for 2 Detectors per System Controller > Range 10 to 80 meters, (33ft to 262ft) configurable per set of Detectors > Integral Laser Alignment in Receiver > 2-wire Interface between Controller and Receiver > Separate Fire and Fault Relays per Detector > Remote/low Level Controller with LCD display (Safe Area) > Programmable Sensitivity and Fire/Fault delay > Contamination Compensation for dust and building movement > Multiple cable gland knock-outs for ease of wiring > Transmitter can be powered from Controller > Complies with ATEX, RoHS and WEEE > Light Cancellation Technology > Supplied with Cable Gland Type E (Double Compression for Armoured Cables), VdS approved > 5 year warranty |
Manufacturer | Fire Fighting Enterprises |
---|---|
MPN | 3000-115 |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Product: | FireRay 3000 Exd End-to-End Explosive Proof Beam Smoke Detector system |
Product code: | 3000-115 |
Dimensions: Control unit Transmitter & Receiver | W:203mm x H:124mm x D:73.5mm W:149mm x H:172mm x D:190mm |
Operating range: | 10 - 80 m (33ft to 262ft) |
Operating voltage range: | 12 - 36 VDC + 10% |
Operating controller current: | 1 or 2 receivers: 14mA constant |
Operating transmitter current: | 8 mA per transmitter |
Power down reset time: | > 20 seconds |
Fire & fault relay contacts: | VFCO 2A @ 30V DC resistive |
Optical wavelength: | 850 nm |
Cable gland entries: Peppers E3WBF Exd Cable Gland | 3 x 20mm E - type of gland featuring armour specific clamping 3 - silicone W - SWA B - brass F - multiple certification |
Operating temperature: | -10 to +55 °C |
Storage temperature: | -20 to +55 °C |
LED indications Control unit: Receiver: | Red=fire, amber=fault, green=system ok Alignment LEDs for single person alignment |
Humidity: | 93% (non-condensing) |
IP Rating: | IP54 (controller), IP66 (transmitter/receiver) |
Parts list System: Additional detector: | 1x transmitter (clear lens), 1x receiver (dark lens), 1x control unit, 1x fixing kit, 2x brackets 1x transmitter (clear lens), 1x receiver (dark lens), 1x fixing kit, 2x brackets |
Housing material Transmitter, receiver: Controller: Bracket: | Copper free aluminium alloy LM25, red UL94 V2 PC Steel, red |
ATEX approval: | SIRA 15ATEX1260 IECEx SIR 15.0089 |
Vds: | EN54 Part 12 |