This website uses cookies to ensure you get the best experience on our website. Read our cookie policy
SKU
FC-315-WA2
£92.22 £76.85
EMS FireCell FC-315-WA2 Red Wall Sounder Beacon Only
- Buy 10 for £87.97 £73.31 each and save 5%
The EMS FireCell FC-315-WA2 is a red wall mounted sounder and category W-3.1-11.3 VAD only which is quick and easy to install. Features include dual band 868MHz operation, auto adjusting power output, 32 selectable tones, 0.5Hz/1Hz beacon ash selection, integrated audio monitoring, volume control and anti tamper locking mechanism.
This device is third party EN certied and compatible with the EMS FireCell system, EMS Fusion Radio Loop Module (RLM) and EMS Wireless Zone Monitor (WZM).
Key Features |
---|
> Red sounder VAD head only > Wall mounted applications > Dual band 868MHz > 32 selectable tones > 0.5Hz/1Hz beacon flash selection > Integrated audio monitoring > Volume control > Anti tamper locking mechanism > EN 54-3, 54-23, 54-25 certified (3rd party) |
Manufacturer | EMS |
---|---|
MPN | FC-315-WA2 |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Dimensions: | Ø:120mm x D:145mm |
Supply: Caution: Fitting of incorrect battery type invalidates the product certification & may result in poor performance | 3 x AA alkaline (Panasonic LR6AD Powerline / Varta 4006 Industrial) & 3 x C alkaline (Panasonic LR14AD Powerline / Varta 4014 Industrial) |
Operating frequency: | 868 MHz |
Output transmitter power: | Auto adjusting 0 to 14dBm (0 to 25mW) |
Sounder output: | 94 - 97 dBA @ 1m Low volume reduces volume by 7dB |
Beacon element current max. | 45mA @ 1Hz flash rate |
Beacon element voltage: | 17 - 60 VDC operating @ 18 VDC |
Beacon coverage: | 3.1 - 11.3 |
Flash rate: | 0.5Hz / 1Hz (selectable) |
IP Rating: | IP54 |
Operating temperature: | -10oC to +55oC |
Storage temperature: | 5oC to 30oC |
Humidity: | 0 - 95% non-condensing |
Location: | Type A: for indoor use |
Weight: | 0.65 kg |