AirSense Stratos HSSD2 is designed to provide high sensitivity smoke detection, ensuring the earliest warning of incipient fire with minimum rate of nuisance alarms.

ClassiFire Perceptive Artificial Intelligence ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.

Upgradable volt-free Fire and Fault relay outputs are available for remote monitoring by local fire detection or BMS systems.

Typical Applications:

• Data storage units
• Prison cells
• Plant rooms
• Air conditioning units
• Equipment racks
• Computer rooms
• Air duct protection
• Heritage property protection
• Critical equipment
• Anti-smoking enforcement
• Motor rooms


Key Features
> High sensitivity provided by laser-based forward light scatter for reliable early warning
> Combined sampling pipe up to 200m in length (still air)
> Unique ClassiFire® Perceptive Artificial Intelligence system that adjusts the detector’s operating parameters, allowing for day-to-day changes in the protected environment and dust separation system contamination
> Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and Elimination system
> RS485 communications built in as standard for networking and remote communications
> Large area aspirating smoke detector, up to 2000m² coverage
> CPR, LPCB, VdS, NF, CSIRO, UL & FM approved
More Information
ManufacturerAirSense
MPN9-30621
Write Your Own Review
You're reviewing:AirSense Stratos HSSD 2
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Code: 9-30621
Description: AirSense Stratos HSSD2 High Sensitivity Smoke Detector
Dimensions: W:427mm x H:372mm x D:95mm
Status indication: LED and LCD
User interface: Keypad
Operating voltage: 21.6 to 26.4 VDC
Input: Standard: 3-programmable
Output: Standard: 5 - Pre-Alarm,​ Alarm,​ Alarm2,​ Aux Alarm (n/o) and Fault (n/c)
Rating: 500mA @ 30V
Current consumption:
450 mA at fan speed 8
Detection principle: Laser light scattering mass detection and particle evaluation
Particle sensitivity range: 0.003μ to 10μ
Measurement range (%Obs/m): 0.0015% to 25%
Alarm levels: 4 (Aux,​ Pre-alarm,​ Alarm and Alarm 2)
Sampling pipework: Inlets: 4
Length: 100m maximum single run (50m in moving air) 
200m Combined maximum
Diameter: 27mm OD
Holes: up to 100 holes
Exhaust: 1 (optional)
Operating temperature: -10 to +60°C (EN54-20)
Relative humidity: 0 to 90% non-condensing
IP Rating: IP40, Indoor
Material (body): Polycarbonate, Sheet steel enclosure with plastic front cover
Cable entries: 6 x M20
Mounting type: Wall
Colour: Cream
Certification: EN54-20,​ FM,​ UL
Weight: 5.2kg
AirSense Stratos HSSD 2