The Siemens FC361-ZA is a fire control panel (1-loop) to which up to 126 addressed fire detectors and other peripheral devices can be connected.
Compared to the standard design, the FC361-ZA variant features an extra-large Comfort housing for 2x 12 V, 25 Ah batteries and an integrated LED indicator for 16 zones.
The control panel is ideally suited to smaller fire detection installations, such as the kind used in workshops, smaller hotels, schools, stores, residential homes, and so on.
The integrated 'Panel Configurator' enables the configuration to be changed quickly and easily on a PC/laptop, without the need for additional software.
Accessories and extensions must be ordered separately.
Key Features |
---|
> Two collective horn lines > Three freely programmable relay outputs > Four freely programmable control inputs/outputs > Optional RS232 module for printer connection > Optional RS485 module for ESPA pager module or DMS > Optional module with four freely configurable monitored outputs > Integrated web-server-based 'FC360 Panel Configurator' software, access via Ethernet connection (port) > Installation space for optional components: LED indicator (32 zones), Key switch (standard) or key switch (Nordic), Evacuation module (NL) > Emergency power supply for emergency operating time of up to 72 hours |
Manufacturer | Siemens |
---|---|
MPN | FC361-ZA |
Primary Power Source | Mains Powered (230V) |
System Type | Addressable |
Number of Loops | 1 |
Number of Zones | 32 |
Protocol Compatibility | Siemens Cerberus |
Colour | Grey |
Warranty | 5 Years |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Standard | EN 54-2 , EN 54-4 , EN 54-13 |
Number of addresses | 126 |
Number of detector lines | Loops: 1 Stub lines: 2 |
Programmable input/output | 4 |
Relay Outputs | 3 NO / NC |
Mains voltage | AC 97...127 V AC 196...253 V |
Operating voltage | DC 20.5…28.6 V |
Operating current | 2500 mA |
Power supply | 70 W |
Bypass time for emergency power supply | 72 h |
Battery capacity | Max. 2x 12 V, 25 Ah |
Plug-in position | 1 for serial interface RS232 or RS485 |
Operating temperature | -5…40 °C |
Storage temperature | -20...+60 °C |
Relative humidity | ≤95% rel. (no condensation) |
Protection category | IP30 |
Color housing/cover | Light grey, ~RAL 7035 |
Weight (net) | 7.74 kg |